SIEMENS

 

Boiler Feed Water Treatment Facility Optimized For A Kentucky Refinery 


Water Technologies

    X

    Contact


    search

    • Water Technologies
      • Products
      • Services
      • Parts
      • Municipal
      • Industries
      • Laboratory
      • Aquatics and Leisure
      • Applications
      • About Us
      • Site Map
      • Contact Us
      • Request A Proposal
    • Applications
      • Aquatic Water Treatment
      • Drinking Water Treatment
      • Groundwater Remediation
      • High Purity Water
      • Industrial Process Water
      • Odor and Vapor Control
      • Oil & Gas Produced Water
      • Sludge & Biosolids Treatment
      • Wastewater Treatment
      • Water Recycle & Reuse
      • Water and Wastewater Library
    • Industrial Process Water
      • Condensate Polishing
      • Organic Chemicals Removal
      • VOC Removal

    Boiler Feed Water Treatment Facility Optimized For A Kentucky Refinery

    Challenge

    A refinery in Kentucky was experiencing difficulties with the quality and quantity of water from their existing water treatment system.  The water was used for the refinery’s boiler feed water treatment facility.  With 18 filters, 10 softeners, a deaerating heater and a reverse osmosis system with pre-filters, plant personnel were overwhelmed with maintenance issues.  Some of the refinery’s specific challenges:

    • Post-precipitation in the filters
    • Lime sludge had entered the filters because of a past clarifier upset
    • Filter media had passed through the filters into the softeners
    • Resin had passed through the softeners into the RO pre-filters and membranes
    • Much of the instrumentation was broken or unreliable
    • The multiport valves had not been regularly maintained


    The process specialist within the refinery’s utilities department needed technical assistance and a quick, dependable solution.

    Solution

    Through our System Optimization Program, a technical services engineer:

    • Traveled to the refinery and conducted a comprehensive review of the entire water treatment system and ancillary equipment
    • Met with operating personnel to determine current maintenance procedures and operating conditions
    • Reviewed operating data and sequences, drawings and operating and maintenance manuals
    • Provided a detailed engineering report, including observations and recommendations


    Results


    Within the engineering report, detailed recommendations were provided for:

    • Cleaning and maintenance procedures for the entire system
    • Replacement components, screens, resins, filter media and instrumentation
    • Alternative materials of construction and sizing of components to provide long-term, reliable operation and ease of maintenance
    • Installation and monitoring procedures
    • Restoration and maintenance procedures for the multiport valves


    In this case, refinery personnel decided not to perform the restoration and maintenance procedures for the multiport valves.  Utilizing the multiport valve restoration program, the valves are being restored to maximum performance.  For each of the valves personnel are:

    • Disassembling
    • Replacing all worn parts and gaskets
    • Lubricating
    • Painting
    • Returning the restored valve to the refinery


    Because of budgetary constraints, the refinery decided upon a 2-year optimization program.  During 2003, 8 filters and 10 softeners were optimized.  During 2004, the remaining 10 filters will be optimized.

    top of page
    Print
    Contact Us
    USFilter can optimize your water treatment system
    Get help now
    Contact

    Related Products

    System Optimization Program
    Permutit Multiport Valves
    Mechanical Upgrade Program
    EnControl Controls Upgrade Program

    © Siemens AG 2009 - Water Technologies
    Corporate Information | Privacy Policy | Terms Of Use | Digital ID